Reply To: Minimum size of vent required

Home Forums Public Forums Drainage & Sewerage Minimum size of vent required Reply To: Minimum size of vent required

#299822
Avatar photoSylvanLMP
Participant

    Ah Mike dont you just wish plumbing were that simple guy?

    Venting is not just fixture units connected BUT developed lenth of pipe and fittings.

    For example I could run 8 FU’s on an 1-1/2 line BUT only for 30 ft BUT I would need a 2″ line to go up to 170 ft.

    Did you now depending on what type of toilet you have how many fixture units it is rated at?

    For example a close couple tank and bowl would be 4 FU and a flushometer type would be 6 FU..

    Why dont you invest in a local code book rather then guessing?