        adding toilet and shower to basement. using 3 plastic pipe connecting to existing 3 iron pipe. need to know how much slope per foot i should have. maximum distance about 8.

      • #305683
        Avatar photoROB IOTT
        Participant

          Minimum slope 1/8 per foot…solids move best at 1/4 per foot… do not exceed 1/2 per foot or the liquids will run ahead of the solids, and they will clog up your pipe. Check your local code regarding the vent…Good luck!: adding toilet and shower to basement. using 3 plastic pipe connecting to existing 3 iron pipe. need to know how much slope per foot i should have. maximum distance about 8.

        • #305684
          Avatar photoROB IOTT
          Participant

            Minimum slope 1/8 per foot…solids move best at 1/4 per foot… do not exceed 1/2 per foot or the liquids will run ahead of the solids, and they will clog up your pipe. Check your local code regarding the vent…Good luck!: adding toilet and shower to basement. using 3 plastic pipe connecting to existing 3 iron pipe. need to know how much slope per foot i should have. maximum distance about 8.

          • #309398
            Avatar photoROB IOTT
            Participant

              We are one of the biggest slope contractor in Hong Kong and we are currently expading our business in trading.Would you like to talk?Regards,John Yau Contracts Manager

            • #309399
              Avatar photoROB IOTT
              Participant

                We are one of the biggest slope contractor in Hong Kong and we are currently expading our business in trading.Would you like to talk?Regards,John Yau Contracts Manager

            Viewing 4 reply threads
            • The forum ‘Old Bulletin Board Archives’ is closed to new topics and replies.

            Pin It on Pinterest

            Share This