A.O. Smith Boiler Problems

Home Forums Public Forums Gas & Gasfitting A.O. Smith Boiler Problems

Viewing 1 reply thread
  • Author
    Posts
    • #278346
      Avatar photoMasterPlumbers
      Keymaster

        I am a very strong trouble shooter, but I can’t get this boiler running. Please help me! We have three 15 year old boilers in a penthouse serving a make up air unit. The boilers are intermitently locking out on pilot failure. We have checked the grounds, replaced the pilot assemblies, tested the gas pressures, and had the gas company come and test the building pressures and replace the regulator. I had two boilders running overnight and one locked out on pilot failure this afternoon. We can reset the boilers, but not know which one will continue to work. HELP ME!

      • #298337
        Avatar photoSelgas
        Participant

          Do these boilers have a pressure switch linked into the control systems for each of them? I ask this question because I had a similar problem here a while ago and the fault albeit intermittent turned out to be the pressure switch circuit. While you are at it have you cleaned out the flues and made sure they do in fact create an upward draught???



          Selgas Services Ltd
          Craftsman Gasfitters, Plumbers, Electrical Service Technicians

      Viewing 1 reply thread