pressure regulator

Home Forums Public Forums General Plumbing pressure regulator

Viewing 1 reply thread
  • Author
    Posts
    • #273089
      Avatar photoMasterPlumbers
      Keymaster

        Di need a pressure reulator? I have 110PSI what is the norm for a house?

      • #286869
        Avatar photoSylvanLMP
        Participant

          Depending which code you use. Some codes require any pressure in excess of 85 PSI must be lowered to this pressure. There is no real “normal” pressure

          Now FYI try to get the actual size and material of your piping (Potable supply) and then figure out the velocity FPS based on Pressure and size giving you a GPM then you can find out the FPS as anything over 8 FPS should be avoided.. Sometimes you need the extra pressure to over come friction losses and and to have certain applications work properly LIKE A flushometer or a fire supression system piped off the domestic main.

          Basically 60+ PSI should cover the majority of applications, again depending on the building height and the lenth of piping involved.

          [Edited by SylvanLMP on 16 June 2000]